Home
Hot Topics
Services
Catalogue
Plant Ex-Stock
Fault Reports
What's On
Tutorials
Safety
About Us

 

Differential Protection

Differential protection is a unit scheme that compares the current on the primary side of a transformer with that on the secondary side.  Where a difference exists (other than that due to the voltage ratio) it is assumed that the transformer has developed a fault and the plant is automatically disconnected by tripping the relevant circuit breakers.  The principle of operation is made possible by virtue of the fact that large transformers are very efficient and hence under normal operation power-in equals power-out.  Differential protection detects faults on all of the plant and equipment within the protected zone, including inter-turn short circuits.

Principle of Operation
The operating principle employed by transformer differential protection is the Merz-Price circulating current system as shown below.  Under normal conditions I1and I2 are equal and opposite such that the resultant current through the relay is zero.  An internal fault produces an unbalance or 'spill' current that is detected by the relay, leading to operation.

 

 

Design Objectives
An ideal scheme is required to be:

bullet

Extremely stable under through fault conditions

bullet

Very fast to operate for an internal fault

Design Considerations

A number of factors have to be taken into account in designing a scheme to meet these objectives.  These include:

bullet

The matching of CT ratios

bullet

Current imbalance produced by tap changing

bullet

Dealing with zero sequence currents

bullet

Phase shift through the transformer

bullet

Magnetising inrush current

Each of these is considered further below.

 

The  Matching of CT Ratios

The CTs used for the Protection Scheme will normally be selected from a range of current transformers with standard ratios such as 1600/1, 1000/5, 200/1 etc.  This could mean that the currents fed into the relay from the two sides of the power transformer may not balance perfectly.  Any imbalance must be compensated for and methods used include the application of biased relays (see below) and/or the use of the interposing CTs (see below).

 

Current Imbalance Produced by Tap Changing

A transformer equipped with an on-load tap changer (OLTC) will by definition experience a change in voltage ratio as it moves over its tapping range.  This in turn changes the ratio of primary to secondary current and produces out-of-balance (or spill) current in the relay.  As the transformer taps further from the balance position, so the magnitude of the spill current increases. To make the situation worse, as the load on the transformer increases the magnitude of the spill current increases yet again.  And finally through faults could produce spill currents that exceed the setting of the relay.  However, none of these conditions is 'in zone' and therefore the protection must remain stable ie. it must not operate.  Biased relays provide the solution (see below).

 

Dealing with Zero Sequence Currents

Earth faults down stream of the transformer may give rise to zero sequence current, depending upon winding connections and earthing arrangements.  Since zero sequence current does not pass through a transformer, it will be seen on one side only producing spill current and possible relay operation for an out-of-zone fault.  To prevent such occurrence, zero sequence current must be eliminated from the differential scheme.  This is achieved by using delta connections on the secondary side of any CTs that are associated with main transformer windings connected in star.

 

Where CT secondaries are connected in star on one side of a transformer and delta on the other, allowance must be made for the fact that the secondary currents outside the delta will only be 1/3 of the star equivalent.

 

Phase Shift Through the Transformer

Having eliminated the problem of zero sequence currents (see above) through faults will still produce positive and negative sequence currents that will be seen by the protection CTs.  These currents may experience a phase shift as they pass through the transformer depending upon the transformer vector group.  CT secondary connections must compensate to avoid imbalance and a possible mal-operation.

 

Magnetising Inrush Current

When a transformer is first energised, magnetising inrush has the effect of producing a high magnitude current for a short period of time.  This will be seen by the supply side CTs only and could be interpreted as an internal fault.  Precautions must therefore be taken to prevent a protection operation.  Solutions include building a time delay feature into the relay and the use of harmonic restraint driven, typically, by the high level of second harmonic associated with inrush current.

 

Other Issues

 

Biased Relays

The use of a bias feature within a differential relay permits low settings and fast operating times even when a transformer is fitted with an on-load tapchanger (see above).  The effect of the bias is to progressively increase the amount of spill current required for operation as the magnitude of through current increases.  Biased relays are given a specific characteristic by the manufacturer.

 

Interposing CTs

The main function of an interposing CT is to balance the currents supplied to the relay where there would otherwise be an imbalance due to the ratios of the main CTs.  Interposing CTs are equipped with a wide range of taps that can be selected by the user to achieve the balance required.

 

As the name suggests, an interposing CT is installed between the secondary winding of the main CT and the relay.  They can be used on the primary side or secondary side of the power transformer being protected, or both.  Interposing CTs also provide a convenient method of establishing a delta connection for the elimination of zero sequence currents where this is necessary.

 

Modern Relays

It should be noted that some of the newer digital relays eliminate the need for interposing CTs by enabling essentials such as phase shift, CT ratios and zero sequence current elimination to be programed directly into the relay.

Tutorial Index

kate spade outlet sport blue 3s louis vuitton outlet louis vuitton outlet louis vuitton outlet foamposites michael kors outlet jordan 6 sport blue louis vuitton outlet louis vuitton outlet louis vuitton outlet beats by dre outlet lebron 12 louis vuitton outlet sport blue 6s louis vuitton outlet louis vuitton outlet retro jordans for sale cheap jordans jordan shine michael kors outlet louis vuitton outlet coach outlet online louis vuitton outlet history of jordan 6s Sport blue 14s jordan 6 sport blue kate spade handbags jordan 6 sport blue legend blue 11s cheap jordans louis vuitton outlet beat by dre cheap michael kors outlet Louis Vuitton Outlet retro jordans for sale louis vuitton outlet louis vuitton outlet Jordan 5 3Lab5 louis vuitton outlet